HomeCapabilitiesProductsCustom WorkContact Us

1:2 Downlink controller

  

Two types of fault inputs may be monitored.

      1)  Dry contact closures where polarity may be set via dip switch setting.

a.       Set S5-1 to “Off” for normally open fault input.  (Closure=fault)

b.      Set S5-1 to “On” for normally closed fault inputs. (Open =fault)

 

2)      Supply current being provided by the controller.

 

Separate Fault type enables:

a.       Set S5-2 to “On” to enable dry contact fault inputs.

b.      Set S5-2 to “Off” to disable dry contact fault inputs.

c.       Set S5-3 to “On” to enable current monitoring faults

d.      Set S5-3 to “Off” to disable current monitoring faults

 

Dry Contact Fault Inputs:

 

These fault inputs are fed into the controller through the rear chassis D-Sub type (Soc) connector J3.  Two pins are allocated for each amplifier.

 

FIG. 3

 

 

 

 

These fault inputs may be configured via a dip switch setting for either a “normally open” or “normally closed” fault input.

 

Dip switch 5 is used for this selection.

Dip switch 5 is a 3 position dip switch.

 

Set S5-1 to “On” for normally closed fault input.  (Open=fault)

Set S5-1 to “Off” for normally open fault inputs. (Closure =fault)

 

Set S5-2 to “On” in order to monitor the contact fault inputs.

Set S5-2 to “Off” in order to ignore the contact fault inputs.

 

Normally open fault defined:

A normally open fault input is defined by this document as a fault input that is “normally open” in a no fault condition.  When the “normally open” fault input closes, a fault is declared.  A closure causes a fault.

 

 

Normally closed fault defined:

A normally closed fault input is defined by this document as a fault input that is “normally closed” in a no fault condition.  When the “normally closed” fault input opens, a fault is declared.  These two fault pins being open (no contact with each other) constitutes a fault condition.

 

Current Monitoring Faults:

 

Setting Up Current Monitoring:

 

When the amplifier is ON, it should be drawing current from a supply inside the controller.  This current is monitored in such a way, that should it deviate from a specified window, a fault is declared.

 

 

Set Dip switch 5-3 to “ON”.  (Factory set to “On”)

This will instruct the DNL-5 to monitor the currents being drawn from the amplifiers.  This monitoring will affect automatic function.

 

When an amplifier operates outside its window for more than a few seconds, a fault is declared.  This fault will show up on the front panel by the associated fault led turning from green to a flashing red.

 

In order to set up an amplifier, a minimal amount of adjustments must be made.  These adjustments allow the DLN-5 to be used with just about any amplifier.  The adjustments are necessary because different amplifiers draw a different amount of current. 

 

For amplifiers that draw >325mA (More than 0.325 Amps), Go to Section 1.2. (In Manual)  (no need to move any jumpers if your amplifiers draw less than 325 mA. @ 24V.)

 

 

Section 1.1 (See fig. 2)

All that really needs to be done is, with an amplifier ON and drawing current, set it’s associated “V Adj” potentiometer to 2.5V.  This is done using potentiometers R3, R11, and R19, for amplifiers A,B,C respectively.  This voltage may be monitored on test points TP1,TP3,TP5 for amplifiers A,B,C respectively.

 

 

Setting Amplifier A:

With a volt meter set up between TP1 (SET 2.5V)  and GND (REF pin), measure the voltage being displayed with amplifier A drawing current.  Rotate potentiometer R3 so that the volt meter reads about 2.5V.

 

 

Setting Amplifier B:

With a volt meter set up between TP3 (SET 2.5V)  and GND (REF pin), measure the voltage being displayed with amplifier B drawing current.  Rotate potentiometer R11 so that the volt meter reads about 2.5V.

 

 

Setting Amplifier C:

With a volt meter set up between TP5 (SET 2.5V)  and GND (REF pin), measure the voltage being displayed with amplifier C drawing current.  Rotate potentiometer R19 so that the volt meter reads about 2.5V.

 

With an amplifier drawing current, and its V ADJ voltage set at 2.5V, the front panel led should be green.

 

 

 

Setting the DELTA voltage:

(IMPORTANT: Please note there should not be any need to adjust the potentiometer R25 (DELTA V). 

 

What is “DELTA V”?

The value of “DELTA V” is what sets up the window around the 2.5V.  This value set up by potentiometer R25 may be measured at TP7.   Typically, the value of this “DELT V” is around 0.5V.  It is set at the factory at 0.6.  The window may be expanded or contracted if desired.

 

 

A current monitored fault is declared when the current being monitored falls outside the “window”.  The “window” is between 2.5V - DELTA V and 2.5V + DELTA V.

Please Note that the amplifier currents are available on the computer port, but these measurements mustn’t be used for any fine measurement purposes.  The A/D converter used on the DNL-5 is an 8-bit device.  That means that each bit is worth 20 mV.  There is a 1:1 relationship between current and voltage with this application, so each bit is worth 20 mA of current.  Therefore, the measurements available on the computer interface port are to be viewed as somewhat coarse numbers only.

 

 

 

 

 

Fault operation:

When an amplifier is in a no fault condition, its associated led should be green on the front panel and the relay indicator on the remote STD port should be open.

 

In the event of a fault, the fault led will go red, and begin to flash on and off.  The audible alarm on the front panel will sound on and off (if the audible enable switch is placed to “ON”).  The relay fault indicator on the remote STD port will become a steady closure.

 

Pushing the “RESET” button on the front panel will extinguish the audible alarm, and cause the fault led to go steady state.  The fault light will always track the true status of the fault.  A blinking green led may signify that a fault had occurred, but then went away.

 

The response time to a closure type fault is immediate.  (keep in mind the time needed to switch a wave guide switch.)

 

The response time to a current fault is a few seconds.  This allows any minor variations that may occur in the amplifier current draw to take place without causing an alarm.                       

 

 

Home           Capabilities             Products           Custom Work           Contact Us